Maximum voltage between any Terminal and Earth Ground
AC 1000 V
DC 1500 V
Batteries 2 AA IEC LR6 alkaline
Display Dual display with backlight
Automatic Power Off 20 minutes
Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, relative humidity at 0 % to 75 %. Accuracy specifications take the form of: ±([% of Reading] + [Number of Least Significant Digits]).
Temperature Coefficients Add 0.1 x specified accuracy for each °C > 28 °C or < 18 °C
AC Current: Jaw
Range 999.9 A
Resolution 0.1 A
Accuracy 2 % + 5 digits (10 Hz to 100 Hz)
2.5 % + 5 digits (100 Hz to 500 Hz)
Crest Factor (50/60 Hz) 2.5 @600.0 A
3.0 @500.0 A
1.42 @999.9 A
Add 2 % for C.F. >2
AC Current: Flexible Current Probe
Range 999.9 A
2500 A
Resolution 0.1 A (≤999.9 A)
1 A (≤2500 A)
Accuracy 3 % RD + 5 digits (10 Hz to 500 Hz)
Crest Factor (50/60Hz) 2.5 @1400 A
3.0 @1100 A
1.42@2500 A
Add 2 % for C.F. >2
Warranty:
As per Brand policy